G.M. International

D1063S

Cena sprzedaży €660,00

Use this text to display some key features of the products

The single channel DIN Rail Load Cell/Strain Gauge Bridge Isolating Repeater D1063S
acts as a transparent galvanic isolated interface installed between a weighing indicator
in Safe Area and a load cell (or group of load cells) in Hazardous Area;
it appears at the terminals of the indicator as a single load cell equivalent to the one
in the field. Provides a fully floating power supply voltage with remote sensing capability
to load cell located in Hazardous Area and repeats, while isolating, the mV signal output
to drive a load in Safe Area depending on the host system reference voltage.
Up to four 350 Ω load cells, or six 450 Ω load cells, or twelve 1000 Ω load cells can be
connected in parallel.
Voltage reference (Safe Area side) is DIP switch configurable to select internal or
external (host system) supply. In addition a field wiring fault red LED indicates any
wire break in the Hazardous Area side.

  • Input from Zone 0 (Zone 20), Division 1, installation in Zone 2, Division 2.
  • Strain Gauge Bridge Transparent Repeater.
  • Up to four 350 Ω load cells in parallel or up to six 450 Ω load cells in parallel or up to twelve 1000 Ω load cells in parallel.
  • Broken field wire fault detection.
  • In-field programmability by DIP switch.

Datasheet